4012: Controller cannot be switched on: Init parameters missing or not valid

Info: Parameter ID
Data type: 'PARID'

Description:
Response error using 'switch on controller' command if at least one Init parameter is missing or was set to an invalid value.

Reaction:
The command is not executed.

Cause/Remedy:
The command was written too soon in the initialization phase, before the configuration was completed.
Parameter initialization or request (delay step) for 'Global init' state is missing.
-> Check program sequence and status request.